Error code Description
8x24h Error in FC/SFC parameter x, where x:
1: Error in DATAPTR
2: Error in DATALEN
8122h Error in parameter DATAPTR (e.g. DB too short)
807Fh Internal error
809Ah interface not found e.g. interface is used by PROFIBUS
809Bh interface not configured
ASCII
Value Description
9000h Buffer overflow (no data send)
9002h Data too short (0byte)
STX/ETX
Value Description
9000h Buffer overflow (no data send)
9001h Data too long (>1024byte)
9002h Data too short (0byte)
9004h Character not allowed
3964R
Value Description
2000h Send ready without error
80FFh NAK received - error in communication
80FEh Data transfer without acknowledgement of partner or error at acknowl-
edgement
9000h Buffer overflow (no data send)
9001h Data too long (>1024byte)
9002h Data too short (0byte)
USS
Error code Description
2000h Send ready without error
8080h Receive buffer overflow (no space for receipt)
8090h Acknowledgement delay time exceeded
80F0h Wrong checksum in respond
Protocol specific RETVAL
values
VIPA SPEED7
Serial Communication
Serial communication > FC/SFC 217 - SER_SND - Send to PtP
HB00 | OPL_SP7 | Operation list | en | 18-30 209