n Input parameter
The input parameters are taken with edge 0-1 at REQUEST. To change parame-
ters, you have to trigger the job again.
If there is again an edge 0-1 at REQUEST during the job processing, an error is
reported, no new command is activated and the answer rejected by the current
command!
n Error handling
The block has 2 error outputs for displaying errors during order processing.
ERROR indicates the error and ERROR_ID shows an additional error number.
The outputs DONE and READ_LENGTH designates a successful command exe-
cution and are not set when ERROR becomes TRUE.
n Behavior of the DONE output
The DONE output is set, when a command was successfully executed.
n Behavior of the BUSY output
The BUSY output indicates that the function block is active.
Busy is immediately set with edge 0-1 of REQUEST and will not be reset until the
job was completed successfully or failed.
As long as BUSY is TRUE, the function block must be called cyclically to execute
the command.
If there is again an edge 0-1 at REQUEST during the job processing, an
error is reported, no new command is activated and the answer rejected
by the current command!
ERROR_ID Description
0x0000 There is no Error
0x8070 Faulty parameter MODE
0x8071 Faulty parameter COMMAND
0x8072 Parameter WRITE_LENGTH exceeds the maximum size
0x8073 Parameter CHANNEL_IN does not fit the parameter MODE
0x8074 Parameter CHANNEL_OUT does not fit the parameter MODE
0x8075 Impermissible command (edge 0-1 at REQUEST during job is exe-
cuted)
0x8081 Error - read access - data do not exist
Command rejected!
0x8091 Error - write access - data do not exist
Command rejected!
0x8092 Error - write access - data out of range
Command rejected!
0x8093 Error - write access - data can only be read
Command rejected!
0x8094 Error - write access - data are write protected
Command rejected!
0x8099 Error during acyclic communication
Command rejected!
ERROR_ID
VIPA SPEED7
Device Specific
Motion Modules > FB 320 - ACYC_RW - Acyclic access to the System SLIO motion module
HB00 | OPL_SP7 | Operation list | en | 18-30 275