No. Parameters that differ from the standard Setting for Simple Motion Control Library
H1-02 Terminal S2 function selection
n 0041: Reverse Run Command
H2-01 Terminal MA/MB-MC selection
n 000E: Fault
H2-02 P1 terminal selection
n 0006
H6-01 Pulse train input function selection
n 0: Frequency reference
H6-02 Pulse train input scaling
n 20000Hz
H6-03 Pulse train input gain
n 100.0%
H6-04 Pulse train input bias
n 0.0%
H6-05 Pulse train input filter time
n 0.10s
H6-06 Pulse train monitor selection
n 102: Output frequency
H6-07 Pulse train monitor scaling
n 20000Hz
No. Parameters depending on the application Example
C1-01 Acceleration time 1
n 10.00s
C1-02 Deceleration time 1
n 10.00s
C1-10 Accel/Decel time setting unit
n 0: 0.01- second units
C1-11 Accel/Decel switching frequency
n 0.0Hz
O1-02 Monitor selection after power up
n 1: Frequency reference
O1-03 Display scaling
n 2: min-1 unit
For all settings to be accepted, you must restart the inverter drive after
parametrization!
VIPA SPEED7
Motion control - Simple Motion Control Library
Usage inverter drive via PWM > Set the parameters on the inverter drive
HB00 | OPL_SP7 | Operation list | en | 18-30 431