Com-
mand
Operand Parameter Function Length
in words
L STW Load status word in ACCU1
T STW Transfer ACCU1 (bits 0 ... 8) into status word
Status word for: L STW BR CC1 CC0 OV OS OR STA RLO /FC
Instruction depends on
ü ü ü ü ü ü ü ü
0
Instruction influences - - - - - - - - -
Status word for: T STW BR CC1 CC0 OV OS OR STA RLO /FC
Instruction depends on - - - - - - - - -
Instruction influences
ü ü ü ü ü
- -
ü
-
Load the number/length of a data block to ACCU1. The old contents of ACCU1 are saved
into ACCU2.
The condition code bits are not affected.
Com-
mand
Operand Parameter Function Length
in words
L DBNO Load number of data block 1
L DINO Load number of instance data block 1
L DBLG Load length of data block into byte 1
L DILG Load length of instance data block into byte 1
Load and transfer instruc-
tions for the status word
Load instructions for DB
number and DB length