RET_VAL (Return value)
Value Description
0000h No error has occurred.
8090h OB_NR parameter error
80A0h No start date/time was defined for the respective time-of-day interrupt OB.
14.1.22.4 SFC 30 - ACT_TINT - Activate time-of-day interrupt
The SFC 30 ACT_TINT (activate time-of-day interrupt) is used to activate the specified
time-of-day interrupt - organization block.
Parameters
Parameter Declaration Data type Memory block Description
OB_NR INPUT INT I, Q, M, D, L,
constant
Number of the OB to be activated
(OB 10, OB 11)
RET_VAL OUTPUT INT I, Q, M, D, L The return value contains an error code if an error
is detected when the function is being processed.
RET_VAL (Rückgabewert)
Value Description
0000h No error has occurred.
8090h OB_NR parameter error
80A0h No start date/time was defined for the respective time-of.-day interrupt OB
80A1h The activated time has expired; this error can only occur when the function is executed once only.
14.1.22.5 SFC 31 - QRY_TINT - Query time-of-day interrupt
The SFC 31 QRY_TINT (query time-of-day interrupt) can be used to make the status of
the specified time-of-day interrupt - organization block available via the output parameter
STATUS.
Parameters
Parameter Declaration Data type Memory block Description
OB_NR INPUT INT I, Q, M, D, L,
constant
Number of the OB, whose status will be queried
(OB 10, OB 11).
RET_VAL OUTPUT INT I, Q, M, D, L The return value contains an error code if an error
is detected when the function is being processed.
STATUS OUTPUT WORD I, Q, M, D, L Status of the time-of-day interrupt.
VIPA SPEED7
Integrated Standard
System Functions > SFC 28 ... SFC 31 - Time-of-day interrupt
HB00 | OPL_SP7 | Operation list | en | 18-30 673