Error code Description
8x7Fh Internal Error. This error code indicates an internal error at parameter x. This error did not result from
the actions if the user and he/she can therefore not resolve the error.
8x01h Illegal syntax detection for an ANY parameter.
8x22h Area size error when a parameter is being read.
8x23h Area size error when a parameter is being written. This error code indicates that parameter x is
located either partially or fully outside of the operand area or that the length of the bit-field for an
ANY-parameter is not divisible by 8.
8x24h Area size error when a parameter is being read.
8x25h Area size error when a parameter is being written. This error code indicates that parameter x is
located in an area that is illegal for the system function. The description of the respective function
specifies the areas that are not permitted for the function.
8x26h The parameter contains a number that is too high for a time cell. This error code indicates that the
time cell specified in parameter x does not exist.
8x27h The parameter contains a number that is too high for a counter cell (numeric fields of the counter).
This error code indicates that the counter cell specified in parameter x does not exist.
8x28h Orientation error when reading a parameter.
8x29h Orientation error when writing a parameter. This error code indicates that the reference to parameter
x consists of an operand with a bit address that is not equal to 0.
8x30h The parameter is located in the write-protected global-DB.
8x31h The parameter is located in the write-protected instance-DB. This error code indicates that parameter
x is located in a write-protected data block. If the data block was opened by the system function itself,
then the system function will always return a value 8x30h.
8x32h The parameter contains a DB-number that is too high (number error of the DB).
8x34h The parameter contains a FC-number that is too high (number error of the FC).
8x35h The parameter contains a FB-number that is too high (number error of the FB). This error code indi-
cates that parameter x contains a block number that exceeds the maximum number permitted for
block numbers.
8x3Ah The parameter contains the number of a DB that was not loaded.
8x3Ch The parameter contains the number of a FC that was not loaded.
8x3Eh The parameter contains the number of a FB that was not loaded.
8x42h An access error occurred while the system was busy reading a parameter from the peripheral area of
the inputs.
8x43h An access error occurred while the system was busy writing a parameter into den peripheral area of
the outputs.
8x44h Error during the n-th (n > 1) read access after an error has occurred.
8x45h Error during the n-th (n > 1) write access after an error has occurred. This error code indicates that
access was denied to the requested parameter.