i-th associated value It is valid 1 ≤ i ≤ maxNumber. The max. number of associated values
may be found in the technical data of your CPU. Permitted are only data of the type
BOOL, (not permitted: bit field), BYTE, CHAR, WORD, INT, DWORD, DINT, REAL,
DATE, TOD, TIME, S5TIME, DATE_AND _TIME.
When the ANY pointer accesses a DB, the DB always must be specified.
(e.g.: P# DB10.DBX5.0 Byte 10).
ERROR = TRUE indicates that an error has occurred during processing. For details refer
to parameter STATUS. The following table contains all the error information specific to
SFB 35 that can be output with the ERROR and STATUS parameters.
ERROR STATUS (dec-
imal)
Description
0 11 Message lost: The previous signal change or the previous message could not be
sent and will be replaced by the current message.
0 22
n Error in the pointer to the associated values SD_i:
– relating to the data length or the data type
– No access to associated values in user memory, for example, due to deleted
DB or area length error. The activated message is sent without associated
values.
n The actual parameter you have selected for SEVERITY is higher than the per-
mitted range. The activated message is sent with SEVERITY = 127.
0 25 Communication was initiated. The message is being processed.
1 1 Communication problems: Disconnection or no logon With acknowledgement-trig-
gered reporting active: temporary display, if no display devices support acknowl-
edgement-triggered reporting.
1 4 At the first call the specified EV_ID is outside the permitted range or the ANY pointer
SD_i has a formal error or the maximum memory area that can be sent for the CPU
per SFB 35 was exceeded.
1 10 Access to local user memory not possible (for example, access to a deleted DB)
1 12 When the SFB was called: an instance DB that does not belong to SFB 34 was
specified or a shared DB instead of an instance DB was specified.
1 18 EV_ID was already being used by one of the SFBs 31 or 33 ... 36.
1 20 Not enough working memory.
1 21 The message with the specified EV_ID is disabled.
After the first block call. all the bits of the ACK_STATE output are set and
it is assumed that the previous values of inputs SIG_i, 1≤ i ≤ 8 were 0.
SD_i
Error information ERROR /
STATUS
VIPA SPEED7
Integrated Standard
System Function Blocks > SFB 35 - ALARM_8P - Messages with associated values (8x)
HB00 | OPL_SP7 | Operation list | en | 18-30 758