EasyManua.ls Logo

YASKAWA VIPA SPEED7 - Page 836

YASKAWA VIPA SPEED7
1007 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Declaration Data Type Description
I_SEL INPUT BOOL INTEGRAL ACTION ON
n The PID actions can be activated or deactivated
individually in the PID algorithm. The I action is on
when the input I_SEL is set.
n Default: TRUE
INT_HOLD INPUT BOOL INTEGRAL ACTION HOLD
n The output of the integrator can be "frozen" by set-
ting the input INT_HOLD.
n Default: FALSE
I_ITL_ON INPUT BOOL INITIALIZATION OF THE INTEGRAL ACTION
n The output of the integrator can be connected to
the input I_ITL_VAL by setting the input I_ITL_ON.
n Default: FALSE
D_SEL INPUT BOOL DERIVATIVE ACTION ON
n The PID actions can be activated or deactivated
individually in the PID algorithm. The D action is on
when the input D_SEL is set.
n Default: FALSE
CYCLE INPUT TIME SAMPLE TIME
n The time between the block calls must be constant.
The CYCLE input specifies the time between block
calls.
n Default: T#1s
n Range of Values: ³ 1ms
SP_INT INPUT REAL INTERNAL SETPOINT
n The SP_INT input is used to specify a setpoint.
n Default: 0.0
n Range of Values: -100.0...100. 0 (%) or phys.
value
1
PV_IN INPUT REAL PROCESS VARIABLE IN
n An initialization value can be set at the PV_IN input
or an external process variable in floating point
format can be connected.
n Default: 0.0
n Range of Values: -100.0...100. 0 (%) or phys.
value
1
PV_PER INPUT WORD PROCESS VARIABLE PERIPHERY
n The process variable in the I/O format is connected
to the controller at the PV_PER input.
n Default: W#16#0000
MAN INPUT REAL MANUAL VALUE
n The MAN input is used to set a manual value using
the operator interface functions.
n Default: 0.0
n Range of Values: -100.0...100. 0 (%) or phys.
value
2
VIPA SPEED7
Standard
PID Control > FB 41 - CONT_C - Continuous control
HB00 | OPL_SP7 | Operation list | en | 18-30 836

Table of Contents

Related product manuals