Parameter Declaration Data type Description
LMNR_HS INPUT BOOL HIGH LIMIT SIGNAL OF REPEATED MANIPULATED
VALUE
n The signal "valve at upper limit stop" is connected
to the LMNR_HS.
n LMNR_HS = TRUE: The valve is at the upper limit
stop.
n Default: FALSE
LMNR_LS INPUT BOOL LOW LIMIT SIGNAL OF REPEATED MANIPULATED
VALUE
n The signal "valve at upper lower stop" is connected
to the input LMNR_LS.
n LMNR_LS = TRUE: The valve is at the lower limit
stop.
n Default: FALSE
LMNS_ON INPUT BOOL MANIPULATED SIGNALS ON
n The processing of the controller output signal is set
to manual at the LMNS_ON input.
n Default: TRUE
LMNUP INPUT BOOL MANIPULATED SIGNALS UP
n With the controller output signals set to manual, the
QLMNUP output signal is applied to the LMNUP
input.
n Default: FALSE
LMNDN INPUT BOOL MANIPULATED SIGNALS DOWN
n With the controller output signals set to manual, the
QLMNDN output signal is applied to the LMNDN
input.
n Default: FALSE
QLMNUP OUTPUT BOOL MANIPULATED SIGNAL UP
n If the QLMNUP output is set, the valve will be
opened.
n Default: FALSE
QLMNDN OUTPUT BOOL MANIPULATED SIGNAL DOWN
n If the QLMNDN output is set, the valve will be
closed.
n Default: FALSE
PV OUTPUT REAL PROCESS VARIABLE
n The effective process variable is output at the PV
output.
n Default: 0.0
PE OUTPUT REAL ERROR SIGNAL
n The effective error is output at the PE output.
n Default: 0.0
COM_RST INPUT/ OUTPUT BOOL COMPLETE RESTART
n The block has an initialization routine that is pro-
cessed when the COM_RST input is set.
n Default: FALSE
VIPA SPEED7
Standard
PID Control > FB 59 - TCONT_S - Temperature Step Control