Variable Type
OB86_RESERVED_2 BYTE
OB86_MDL_ADDR WORD
OB86_Z23 DWORD
OB86_DATE_TIME DATE_AND_TIME
The following table shows the event started OB 86:
EV_CLASS FLT_ID Variable Bit ... Description
39h, 38h C4h Failure of a DP station
C5h Fault in a DP station
C4h, C5h OB86_MDL_ADDR Logical base address of the DP
master
OB86_Z23 Address of the affected DP slave:
Bit 7 ... 0 Number of the DP station
Bit 15 ... 8 DP master system ID
Bit 30 ... 16 Logical base address of the DP
slave
Bit 31 I/O identifier
38h C7h Return of a DP station, but error
in module parameter assignment
OB86_MDL_ADDR Logical base address of the DP
master
OB86_Z23 Address of the DP slaves
affected:
Bit 7 ... 0 Number of the DP station
Bit 15 ... 8 DP master system ID
Bit 30 ... 16 Logical base address of the DP
slave
Bit 31 I/O identifier
C8h Return of a DP station, however
discrepancy in configured and
actual configuration
OB86_MDL_ADDR Logical base address of the DP
master
OB86_Z23 Address of the DP slaves
affected:
Bit 7 ... 0 Number of the DP station
Bit 15 ... 8 DP master system ID
Bit 30 ... 16 Logical base address of the DP
slave
Bit 31 I/O identifier
VIPA SPEED7
Organization Blocks
Asynchronous error Interrupts > OB 86 - RACK_FLT - Slave Failure / Restart
HB00 | OPL_SP7 | Operation list | en | 18-30 97