In the case of SSL_ID 0091h and 0F91h two additional record sets are supplied per rack:
n A record for the power supply if it exists
n A record set for the rack
The sequence of the records in case of a centralized structure is:
Power supply, slots 1 ... n, rack
The record set starts always from the first assigned logical I/O address
(basic address).
Record set SSL_ID: xy91h:
INDEX
offset
Name Length Description
0 adr1 1word
Ä
‘adr1’ page 979
2 adr2 1word
Ä
‘adr2’ page 980
4 logadr 1word First assigned logical I/O address (basic address).
6 solltyp 1word Target type: only at PROFINET or EtherCAT (otherwise reserved)
8 isttyp 1word Actual type: only at PROFINET or EtherCAT (otherwise reserved)
10 reserved 1word
n At PROFINET-IO or EtherCAT (otherwise reserved):
– SSL-ID = 0C91h: Number of really existing submodules
(without submodule 0)
– SSL-ID = 0D91h: Number of submodules
(without submodule 0)
– SSL-ID = 4C91h: Number of really existing submodules
(without submodule 0)
– SSL-ID = 4D91h: Number of really existing submodules
(without submodule 0)
12 eastat 1word
n I/O status:
– Bit 0: 1: Module error (detected by diagnostic interrupt)
– Bit 1: 1: Module exists
– Bit 2: 1: Module does not exist
– Bit 3: 1: Module disabled
– Bit 4: 1: Station error
– Bit 5: 1: A CiR event at this module /station is busy or not yet completed.
– Bit 6: 1: reserved
– Bit 7: 1: Module in local bus segment
– Bit 8 ... 15: Data ID for logical address
(Input: B4h, Output: B5h, DP interface: FFh)
14 ber_bgbr 1word
n Area ID/module width
– Bit 0 ... 2: Module width
– Bit 3: reserved
– Bit 4 ... 6: Area ID
0: Siemens S7-400
1: Siemens S7-300
Additional Record sets
VIPA SPEED7
SSL System status list
Status information CPU - SSL-ID: xy91h
HB00 | OPL_SP7 | Operation list | en | 18-30 978