EasyManuals Logo

Agilent Technologies E4406A VSA Series User Manual

Agilent Technologies E4406A VSA Series
420 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #300 background imageLoading...
Page #300 background image
300 Chapter5
Language Reference
SENSe Subsystem
Channel Power—Averaging Termination Control
[:SENSe]:CHPower:AVERage:TCONtrol EXPonential|REPeat
[:SENSe]:CHPower:AVERage:TCONtrol?
Select the type of termination control used for the averaging function.
This determines the averaging action after the specified number of data
acquisitions (average count) is reached.
Exponential - Each successive data acquisition after the average
count is reached, is exponentially weighted and combined with the
existing average.
Repeat - After reaching the average count, the averaging is reset and
a new average is started.
Factory Preset
and *RST: Repeat
Remarks: You must be in the cdmaOne, cdma2000, W-CDMA
(3GPP), W-CDMA (Trial & Arib), or Basic mode to use
this command. Use INSTrument:SELect to set the
mode.
Channel Power—Integration BW
[:SENSe]:CHPower:BANDwidth|BWIDth:INTegration <freq>
[:SENSe]:CHPower:BANDwidth|BWIDth:INTegration?
Set the Integration BW (IBW) that will be used.
Factory Preset
and *RST: 1.23 MHz for Basic, cdmaOne, cdma2000
5.0 MHz for W-CDMA (3GPP), W-CDMA (Trial & Arib)
Range: 1 kHz to 10 MHz
Default Unit: Hz
Remarks: You must be in the cdmaOne, cdma2000, W-CDMA
(3GPP), W-CDMA (Trial & Arib), or Basic mode to use
this command. Use INSTrument:SELect to set the
mode.

Table of Contents

Other manuals for Agilent Technologies E4406A VSA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Agilent Technologies E4406A VSA Series and is the answer not in the manual?

Agilent Technologies E4406A VSA Series Specifications

General IconGeneral
BrandAgilent Technologies
ModelE4406A VSA Series
CategoryTest Equipment
LanguageEnglish

Related product manuals