300 Chapter5
Language Reference
SENSe Subsystem
Channel Power—Averaging Termination Control
[:SENSe]:CHPower:AVERage:TCONtrol EXPonential|REPeat
[:SENSe]:CHPower:AVERage:TCONtrol?
Select the type of termination control used for the averaging function.
This determines the averaging action after the specified number of data
acquisitions (average count) is reached.
Exponential - Each successive data acquisition after the average
count is reached, is exponentially weighted and combined with the
existing average.
Repeat - After reaching the average count, the averaging is reset and
a new average is started.
Factory Preset
and *RST: Repeat
Remarks: You must be in the cdmaOne, cdma2000, W-CDMA
(3GPP), W-CDMA (Trial & Arib), or Basic mode to use
this command. Use INSTrument:SELect to set the
mode.
Channel Power—Integration BW
[:SENSe]:CHPower:BANDwidth|BWIDth:INTegration <freq>
[:SENSe]:CHPower:BANDwidth|BWIDth:INTegration?
Set the Integration BW (IBW) that will be used.
Factory Preset
and *RST: 1.23 MHz for Basic, cdmaOne, cdma2000
5.0 MHz for W-CDMA (3GPP), W-CDMA (Trial & Arib)
Range: 1 kHz to 10 MHz
Default Unit: Hz
Remarks: You must be in the cdmaOne, cdma2000, W-CDMA
(3GPP), W-CDMA (Trial & Arib), or Basic mode to use
this command. Use INSTrument:SELect to set the
mode.