CRITICALPOINT 700/800MHZ BDA/DAS/BBU V3 USER MANUAL
©2024 Comba Telecom. All Rights Reserved.
568 Gibraltar Drive, Milpitas, CA 95035 | +1 408 526 0180
Rev. 1-0-2 Rev. Date: 11-1-2024
Page: 202
Table 33 contains a complete list of all internal device alarms. Each of these individual alarms can be
configured to trigger one of the 8 Dry Contact outputs. By default, the V3 BDA/MU/RU devices will use the
NFPA 1221 2019 alarm configuration, and the internal alarms are already configured for that standard. The
user can choose one of the standard presets, or they can use a custom user defined configuration and
configure which internal system alarms are mapped to each Dry Contact Output relay.
Table 33: V3 BDA/MU/RU - Complete List of Device Alarms
Summary
Alarm
Dry Contact
Alarm
Individual System Alarms
Related Bands / Modules / Devices
Yes
Configurable
DL P_in Low Alarm
DL 700MHz, DL 800MHz
Yes
Configurable
DL P_out Low Alarm
DL 700MHz, DL 800MHz
Yes
Configurable
DL P_in Over Alarm
DL 700MHz, DL 800MHz
Yes
Configurable
DL P_out Over Alarm
DL 700MHz, DL 800MHz
Yes
Configurable
LNA Alarm
DL 700MHz, DL 800MHz, UL
700/800MHz
Yes
Configurable
PA Alarm
DL 700MHz, DL 800MHz, UL
700/800MHz
Yes
Configurable
PA Shutdown Alarm
DL 700MHz, DL 800MHz, UL
700/800MHz
Yes
Configurable
VSWR Alarm
DL 700MHz, DL 800MHz
Yes
Configurable
Oscillation Shutdown Alarm
700MHz, 800MHz, hidden when the
feature is OFF
Yes
Configurable
Oscillation Gain Reduction Alarm
700MHz, 800MHz, hidden when the
feature is OFF
Yes
Configurable
Digital Clock Lock Alarm
Device
Yes
Configurable
PLL Alarm
Device
Yes
Configurable
DT ANT Disconnection Alarm
Device
Yes
Configurable
Over Temperature Alarm
Device
Yes
Configurable
External Alarms 1-4
Device
Yes
Configurable
External Alarm 5
Device / Preconfigured as Door
Open Alarm
Yes
Configurable
Loss Of Normal AC Power
BBU, hidden when not using BBU V3
Yes
Configurable
Battery Low Alarm
BBU, hidden when not using BBU V3
Yes
Configurable
Charger Fault Alarm
BBU, hidden when not using BBU V3
Yes
Configurable
Battery Over-Discharge Alarm
BBU, hidden when not using BBU V3
Yes
Configurable
Battery Over Temperature Alarm
BBU, hidden when not using BBU V3
Yes
Configurable
Battery Connection Fail Alarm
BBU, hidden when not using BBU V3
Yes
Configurable
Battery Comm. Fault Alarm
BBU, hidden when not using BBU V3
Yes
Configurable
Charger Comm. Fault Alarm
BBU, hidden when not using BBU V3
Yes
Configurable
System Dry ALM 1
RU Dry Contact 1 Alarm