EasyManua.ls Logo

COMBA CriticalPoint V3 7 BDA - Page 72

Default Icon
257 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CRITICALPOINT 700/800MHZ BDA/DAS/BBU V3 USER MANUAL
©2024 Comba Telecom. All Rights Reserved.
568 Gibraltar Drive, Milpitas, CA 95035 | +1 408 526 0180
Rev. 1-0-2 Rev. Date: 11-1-2024
Page: 72
Figure 44: EPO Switch Wiring Diagram
Table 5: V3 BBU and EPO Relay Specifications
Parameter
Value
EPO Relay Control Circuit Voltage:
24-60VDC
EPO Relay Current:
<100mA
BBU Battery Nominal Voltage
51.2VDC
BBU Cut-off Threshold
46VDC
EPO Installation Notes:
1. The EPO connections have a pre-installed wire that shunts the EPO+ and EPO- terminals. Remove
the pre-installed wire and connect the EPO switch; then turn the EPO switch to its “Closed” position
(Normal Status).
2. DO NOT set the EPO switch to “Open” (Cut-off Status).
3. The EPO switch can be installed at a remote location, but the voltage drop should be considered
before installing.
4. The EPO function is triggered from a relay and this relay is energized by the battery or the charger; if
the battery is over-discharged, then the EPO function may not work properly.
5. If you do not wish to use an EPO switch, do NOT remove the pre-installed shorting wire!
V3 BBU

Table of Contents