EasyManua.ls Logo

Copeland E3 - Page 173

Copeland E3
241 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
©2025 Copeland LP.
026-1803 R13 Supervisor I&O User Guide B - 3
Problems with Temp Sensor or
Pressure Transducer Displaying
Proper Value
16AI input dip switches are
set incorrectly.
The 16 dip switches on the 16AI board correspond
to each of the inputs:
Dip Switches Up = Temperature Sensor
Dip Switches Down = Pressure Transducer
Incorrect board and point
address.
Set proper board and point settings for both input
and output: Go to the Inputs tab in the application’s
Setup screen and check Board and Point.
Incorrect sensor type.
Verify that the sensor type in Site Supervisor is the
same as the sensor installed. (For example, “5V-
200PSI” is a 5-volt powered 200PSI pressure trans-
ducer, and “Temperature” is the standard Copeland
temperature sensor.
NOTE: The previous Eclipse and Standard sensors
are now 5V and 12V respectively.
For 16AI boards:
For Onboard I/O:
1. Log into the Supervisory Controller.
2. Click the
Site Map icon.
3. Under
Control Status, select System.
4. Click
Onboard IO along the bottom of the screen.
5. Click
Details.
6. Under
Onboard IO DETAILS, click Setup.
7. Check the desired sensor type value from the list
and click
Edit to make changes.
No Heat Will Come On
Incorrect board and points
assignment. Check the Heat
OAT lockout temps.
Make sure that your board and points are assigned
to the correct compressors and heat stages.
1. Log into the Supervisory Controller.
2. Click the
Site Map icon.
3. Under
Control Status, click HVAC.
4. Click
Details.
5. If
Heat Lockout En is enabled (set to ON), check
that Heat OAT LOCK is set to a valid setpoint
(temperature) for heat lock out.
No Cooling Will Come On
Incorrect board and points
assignment. Check the Cool
OAT lockout temps.
Make sure that your board and points are assigned
to the correct compressors and heat stages.
1. Log into the Supervisory Controller.
2. Click the
Site Map icon.
3. Under
Control Status, click HVAC.
4. Click
Details.
5. If
Cool Lockout En is enabled (set to ON), check
that Cool OAT LOCK is set to a valid setpoint
(temperature) for cool lock out.
SYMPTOM POSSIBLE PROBLEM SOLUTION

Table of Contents