Chapter 4 Parameters
4-89
Bit setting
bit3
MO2
bit2
MO1
bit1
RA
bit0
MRA
Pr02-15
0 0 0 0 0
0 0 0 1 1
0 0 1 0 2
0 0 1 1 3
0 1 0 0 4
0 1 0 1 5
0 1 1 0 6
0 1 1 1 7
1 0 0 0 8
1 0 0 1 9
1 0 1 0 10
1 0 1 1 11
1 1 0 0 12
1 1 0 1 13
1 1 1 0 14
1 1 1 1 15
02-16 Terminal Count Value Unit:1
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory setting: 0
Settings 0 ~ 65535
The counter trigger can be set by the multi-function terminal MI6 (set Pr.02-06 to 23).
Upon completion of counting, the specified output terminal will be activated (Pr.02-11 to
Pr.02-14 is set to 17).
When the display shows c5555, the drive has counted 5,555 times. If display shows
c5555, it means that real counter value is between 55,550 to 55,559.
02-17 Preliminary Count Value Unit:1
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory setting: 0
Settings 0 ~ 65535
When the counter value reaches this value, the corresponding multi-function output
terminal will be activated, provided one of Pr. 02-11 to 02-14 set to 18 (Preliminary
Count Value Setting). This parameter can be used for the end of the counting to make
the drive runs from the low speed to stop.