Chapter 4 Parameters
4-139
shut off the output and wait until the command frequency rises above Pr. 08-11. Please
see the below diagram.
08-11
08-10
08-12
0Hz
Sleep Function
Frequency command
actual output frequency
sleep time
Wake-up frequency
Sleep frequency
08-13 PID Deviation Level Unit: 0.1
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 10.0
Settings 1.0 to 50.0%
08-14 PID Deviation Time Unit: 0.1
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 5.0
Settings 0.1 to 300.0 sec
08-15 Filter Time for PID Feedback Unit: 0.1
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 5.0
Settings 0.1 to 300.0 sec
08-16 Reserved
08-17 Reserved
08-18 Reserved
08-19 Reserved
08-20 Reserved