Chapter 4 Parameters
4-138
08-08 Feedback Signal Detection Time Unit: 0.1
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 0.0
Settings 0.0 to 3600.0 sec
This parameter is only valid when the feedback signal is ACI.
This parameter defines the time during which the PID feedback must be abnormal
before a warning is given. It also can be modified according to the system feedback
signal time.
If this parameter is set to 0.0, the system would not detect any abnormality signal.
08-09 Feedback Fault Treatment
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 0
Settings 0 Warn and keep operating
1 Warn and RAMP to stop
2 Warn and COAST to stop
3 Warn and keep at last frequency
This parameter is only valid when the feedback signal is ACI.
AC motor drive acts when the feedback signals (analog PID feedback or PG (encoder)
feedback) are abnormal.
08-10 Sleep Frequency Unit: 0.01
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 0.00
Settings 0.00 to 600.00Hz
08-11 Wake-up Frequency Unit: 0.01
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 0.00
Settings 0.00 to 600.00Hz
08-12 Sleep Time Unit: 0.1
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 0.0
Settings 0.0 to 6000.0sec
These parameters determine sleep functions of the AC drive. If the command frequency
falls below the sleep frequency, for the specified time in Pr. 08-12, then the drive will