Chapter 4 Parameters
4-104
05-05 No-load Current of Motor 1 (A) Unit: Amp
Control
mode
VFPG SVC FOCPG TQCPG
Factory setting: #.##
Settings 0 to factory setting of Pr.05-01
The factory setting is 40% X rated current.
05-06
Stator Resistance(Rs) of Motor 1
Unit: 0.001
05-07
Rotor Resistance(Rr) of Motor 1
Unit: 0.001
Control
mode
SVC FOCPG TQCPG
Factory setting: #.###
Settings
0~65.535
05-08 Magnetizing Inductance(Lm) of Motor 1 Unit: 0.1
05-09 Stator inductance(Lx) of Motor 1 Unit: 0.1
Control
mode
SVC FOCPG TQCPG
Factory setting: #.#
Settings 0~6553.5mH
05-10 Motor 1/Motor 2 Selection
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory setting: 1
Settings 1 Motor 1
2 Motor 2
It is used to set the motor that driven by the AC motor drive.
05-11
Frequency for Y-connection/ connection Switch
Unit: 0.01
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory setting: 60.00
Settings 0.00 to 600.00Hz
05-12
Y-connection /connection Switch
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory setting: 0
Settings 0 Disable
1 Enable
05-30
Delay Time for Y-connection/connection
Unit: 0.001
Control
mode
VF VFPG SVC FOCPG
Factory setting: 0.200
Settings 0 to 60.000
Pr.05-12 is used to enable/disable Y-connection/ connection Switch.