Chapter 4 Parameters
4-184
01-01
or
01-35
11-05
or
11-06
100%
90%
output torque
Flux weakening curve
frequency
11-07 Detection Time for Phase-loss Unit: 0.01
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory Setting: 0.20
Settings 0.01 to 600.00 sec
11-09 Level of Phase-loss Unit: 0.1
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory Setting: 60.0
Settings 0.0 to 320.0
11-29 Accumulative Operation Time of Phase-loss Unit: 1
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory Setting: 0
Settings 0 to 65535 (hour)
When the power phase-loss occurs and it exceeds the level (Pr.11-09) and the detection
time(Pr.11-07), it will execute the phase-loss protection(Pr.06-02). The AC motor drive
will record the operation time during phase-loss in Pr.11-29.
If it is set to 0 or a larger number, it will short the life of rectifier and capacitors in the
AC motor drive.
11-08 Reserved
11-10 Speed Feed Forward Gain Unit: 1
Control
mode
FOCPG
Factory Setting: 0
Settings 0 to 100%
It is used to improve the speed response.