Chapter 4 Parameters
4-81
Settings Functions Descriptions
48
Mechanical Gear Ratio
Switch
When this contact is ON, the mechanical gear ratio switch will
be the second group A2/B2 (refer to Pr.10-29 and Pr.10-30).
49 Enable Drive
When this contact is ON, the output of drive will stop.
MI=d49
RUN
Time
Start running
02-34=0 no action
02-34=1
MI=d49
RUN
Time
Start running
MI=d49
RUN
Time
deceleration to stop
start running from 0Hz
02-34=0 no action
02-34=1
MI=d49
RUN
Time
free run to stop
start running from 0Hz
50 Reserved
02-07 UP/DOWN Key Mode
Control
mode
VF VFPG SVC FOCPG
Factory setting: 0
Settings 0 Up/down by the accel/decel time
1 Up/down constant speed (Pr.02-08)
02-08
The Acceleration/Deceleration Speed of the UP/DOWN Key
with Constant Speed
Unit: 0.01
Control
mode
VF VFPG SVC FOCPG
Factory setting: 0.01
Settings 0.01 ~ 1.00Hz/ms