Chapter 4 Parameters
4-106
Y-connection output
Pr.02-11~14=31
Y-connection
confirmation input
Pr.02-01~06=29
-connection output
Pr.02-11~14=32
-connection
confirmation input
Pr.02-01~06=30
ON
ON
ON
ON
2 seconds
Y- switch error
frequency
free run status
output
frequency
delay time
Pr.05-30
05-13 Full-load Current of Motor 2(A) Unit: Amp
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory setting: #.##
Settings 40 to 120%
This value should be set according to the rated frequency of the motor as indicated on
the motor nameplate. The factory setting is 90% X rated current.
Example: The rated current for 7.5HP (5.5kW) is 25 and factory setting is 22.5A. The
range for setting will be 10~30A.(25*40%=10 and 25*120%=30)
05-14 Rated Power of Motor 2 (kW) Unit: 0.01
Control
mode
SVC FOCPG TQCPG
Factory setting: #.##
Settings 0 to 655.35
It is used to set rated power of the motor 2. The factory setting is the power of the drive.
05-15 Rated Speed of Motor 2 (rpm) Unit: 1
Control
mode
VFPG SVC FOCPG TQCPG
Factory setting: 1710
Settings 0 to 65535
It is used to set the rated speed of the motor and need to set according to the value
indicated on the motor nameplate.