Chapter 4 Parameters
4-93
02-34 External Operation Control Selection after Reset Unit:1
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory setting: 0
Settings 0: Disable
1: Drive runs if run command exists after reset
After clearing fault once a fault is detected and the external terminal for RUN keeps ON,
the drive can run after pressing RESET key.
02-43 Zero-speed Level of Motor Unit: 1
Control
mode
VFPG FOCPG TQCPG
Factory setting: 0
Settings 0~65535rpm
This parameter should be used with the multi-function output terminals (set to 43).
This parameter is used to set the level of motor zero-speed. When the actual speed is
lower than this setting, the corresponding multi-function output terminal 43 will be ON
as shown as follows.
02-43
MO=d43
actual motor
speed
Time