Chapter 4 Parameters
4-95
Positive torque
Reverse
03-00~02=7
Positive torque limit
03-00~02=8
Negative torque limit
03-00~02=9
Regenerative
torque limit
03-00~02=10
Positive/negative torque limit
Negative Torque
Forward
03-00~02=10
Positive/negative torque limit
03-00~02=9
Regenerative
torque limit
03-03 Analog Input Bias 1 (AVI) Unit: 0.1
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory setting: 0
Settings -100.0~100.0%
It is used to set the corresponding AVI voltage of the external analog input 0.
03-04 Analog Input Bias 1 (ACI) Unit: 0.1
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory setting: 0
Settings -100.0~100.0%
It is used to set the corresponding ACI voltage of the external analog input 0.
03-05 Analog Input Bias 1 (AUI) Unit: 0.1
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory setting: 0
Settings -100.0~100.0%
It is used to set the corresponding AUI voltage of the external analog input 0.
03-06 Positive/negative Bias Mode (AVI)
03-07 Positive/negative Bias Mode (ACI)
03-08 Positive/negative Bias Mode (AUI)
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory setting: 0
Settings 0 Zero bias
1 Lower than bias=bias
2 Greater than bias=bias