Chapter 4 Parameters
4-156
08-77 Max. Tension Unit: 1
Control
mode
TQCPG
Factory Setting: 0
Settings 0 ~30000 N
08-78 Tension Setting Unit: 1
Control
mode
TQCPG
Factory Setting: 0
Settings 0 ~30000 N
Pr.08-78 will be read-only when Pr.08-76 is set to 1. The analog input 10V corresponds
to Pr.08-77.
08-79 Source of Zero-speed Tension Setting
Control
mode
TQCPG
Factory Setting: 0
Settings 0 Disable
1 Communication RS-485 (Pr.08-80)
2 Analog input (Pr. 03-00~03-02 is set to 16 zero-speed tension)
(Pr.08-80)
When Pr.08-79 is set to 1, Pr.08-80 setting can be changed by inputting the digital
keypad, HMI page plan, text panel (PLC product: TP series) via communication.
When Pr.08-79 is set to 2 and one of Pr. 03-00~03-02=16, Pr.08-80 only displays tension
setting.
08-80 Setting of Zero-speed Tension Unit: 1
Control
mode
TQCPG
Factory Setting: 0
Settings 0 ~30000 N
Pr.08-80 is read-only when Pr.08-79 is set to 2. The input analog 10V corresponds to
Pr.08-77.
08-81 Source of Tension Taper
Control
mode
TQCPG
Factory Setting: 0
Settings 0 Communication RS-485 (Pr.08-82)
1 Analog input (Pr. 03-00~03-02 is set to 17 tension taper) (Pr.08-82)