Chapter 4 Parameters
4-170
09-07 COM2 Time-out Detection (Keypad) Unit: 0.1
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory Setting: 0.0
Settings 0.0 ~ 100.0 sec
If Pr.09-03 is not equal to 0.0, Pr.09-02=0~2, and there is no communication on the bus
during the Time Out detection period (set by Pr.09-03), “cE10” will be shown on the
keypad.
09-08 COM2 Communication Protocol (Keypad)
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory Setting: 13
Settings 0 Modbus ASCII mode, protocol <7,N,1>
1 Modbus ASCII mode, protocol <7,N,2>
2 Modbus ASCII mode, protocol <7,E,1>
3 Modbus ASCII mode, protocol <7,O,1>
4 Modbus ASCII mode, protocol <7,E,2>
5 Modbus ASCII mode, protocol <7,O,2>
6 Modbus ASCII mode, protocol <8,N,1>
7 Modbus ASCII mode, protocol <8,N,2>
8 Modbus ASCII mode, protocol <8,E,1>
9 Modbus ASCII mode, protocol <8,O,1>
10 Modbus ASCII mode, protocol <8,E,2>
11 Modbus ASCII mode, protocol <8,O,2>
12 Modbus RTU mode, protocol <8,N,1>
13 Modbus RTU mode, protocol <8,N,2>
14 Modbus RTU mode, protocol <8,E,1>
15 Modbus RTU mode, protocol <8,O,1>
16 Modbus RTU mode, protocol <8,E,2>
17 Modbus RTU mode, protocol <8,O,2>
09-09 Response Delay Time Unit: 0.1
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory Setting: 2.0
Settings 0.0 ~ 200.0 msec
This parameter is the response delay time after AC drive receives communication
command as shown in the following.