Chapter 4 Parameters
4-12
Group 5 Motor Parameters
Pr. Explanation Settings
Factory
Setting
VF VFPG
SVC FOCPG
TQCPG
05-00 Motor Auto Tuning 0: No function
1: Rolling test
2: Static Test
3: Reserved
0
05-01 Full-load Current of
Motor 1 (A)
40-120% of drive’s rated current #.##
05-02
Rated power of Motor 1
(kW)
0~655.35 #.##
05-03
Rated speed of Motor 1
(rpm)
0~65535
1710 (60Hz, 4 poles), 1410 (50Hz, 4 poles)
1710
05-04 Number of Motor Poles 1 2~20 4
05-05 No-load Current of Motor
1 (A)
0-factory setting of Pr.05-01 #.##
05-06 Stator Resistance (Rs) of
Motor 1
0~65.535
#.###
05-07 Rotor Resistance (Rr) of
Motor 1
0~65.535
#.###
05-08 Magnetizing Inductance
(Lm) of Motor 1
0~6553.5mH #.#
05-09 Stator inductance (Lx) of
Motor 1
0~6553.5mH #.#
05-10 Motor 1/Motor 2
Selection
1: Motor 1
2: Motor 2
1
05-11
Frequency for Y-
connection/
connection Switch
0.00~600.00Hz 60.00
05-12 Y-connection
/connection Switch
0: Disable
1: Enable
0
05-13 Full-load Current of
Motor 2 (A)
40-120% #.##
05-14
Rated Power of Motor 2
(kW)
0~655.35 #.##
05-15
Rated Speed of Motor 2
(rpm)
0~65535 1710
05-16 Number of Motor Poles 2 2~20 4
05-17 No-load Current of Motor
2 (A)
0- factory setting of Pr.05-01 #.##
05-18 Stator Resistance(Rs) of
Motor 2
0~65.535
#.###
05-19 Rotor Resistance(Rr) of
Motor 2
0~65.535
#.###
05-20 Magnetizing Inductance
(Lm) of Motor 2
0~6553.5mH #.#
05-21 Stator Inductance(Lx) of
Motor 2
0~6553.5mH #.#
05-22
Torque Compensation
Time Constant
0.001~10.000sec 0.020
05-23
Slip Compensation Time
Constant
0.001~10.000sec 0.100
05-24
Torque Compensation
Gain
0~10 0
05-25
Slip Compensation Gain 0.00~10.00 0.00
05-26
Slip Deviation Level 0~1000% (0: disable) 0
05-27
Detection Time of Slip
Deviation
0.0~10.0 sec 1.0
05-28
Over Slip Treatment
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
0
05-29
Hunting Gain 0~10000 (0: disable) 2000
05-30
Delay Time for Y-
connection/connection
0~60.000 sec 0.200
05-31 Accumulative Motor
Operation Time (Min.)
00~1439 0
05-32 Accumulative Motor
Operation Time (day)
00~65535 0