Chapter 4 Parameters
4-121
06-30 PTC Level Unit: 0.1
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory Setting: 50.0
Settings 0.0 to 100.0%
It is used to set the PTC level, and the corresponding value for 100% is max. analog
input value.
06-31 Filter Time for PTC Detection Unit: 0.01
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory Setting: 0.20
Settings 0.00 to 10.00 sec
06-32 Output Frequency for Malfunction
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory Setting: Read-only
Settings 0.00 to 655.35 Hz
06-33 Output Voltage for Malfunction
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory Setting: Read-only
Settings 0.0~6553.5 V
06-34 DC Voltage for Malfunction
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory Setting: Read-only
Settings 0.0~6553.5 V
06-35 Output Current for Malfunction
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory Setting: Read-only
Settings 0.00~655.35 Amp
06-36 IGBT Temperature for Malfunction
Control
mode
VF VFPG SVC FOCPG TQCPG
Factory Setting: Read-only
Settings 0.0~6553.5 °C