Eject the memory module again by pressing out the securing clips at each
end of the memory slot.
â–¶
Press down on the memory module until the securing clips snap into the
cutouts at each end of the module.
â–¶
Check if all securing clips are in the correct position, see Figure 139.
Concluding steps
For memory slots from A to M valid for the bottom system board.
â–¶
Install the air duct on the bottom system board, see "Installing the CPU air
duct" on page 74.
â–¶
"Installing the top system board holder" on page
79.
â–¶
"Installing the riser module 3/4 and 6/7" on page 62.
â–¶
"Installing the fan cage" on page 71.
â–¶
Install the air duct on the top system board, see "Installing the CPU air duct"
on page 74.
â–¶
"Reassembling" on page 53.
â–¶
"Installing the server in the rack" on page 55.
â–¶
"Connecting the power cord (AC PSU)" on page 58.
â–¶
"Switching on the server" on page 59.
â–¶
"Resetting the error status after replacing memory modules or CPU" on
page 97.
â–¶
"Resuming BitLocker functionality" on page 108.
For memory slots from N to Z valid for the top system board.
â–¶
"Installing the CPU air duct" on page 74.
â–¶
"Reassembling" on page 53.
â–¶
"Connecting the power cord (AC PSU)" on page 58.
â–¶
"Switching on the server" on page 59.
â–¶
"Resuming BitLocker functionality" on page 108.