Alarm Handling - List of all alarms
Fusion4 MSC-L Part No.: 4418309_Rev09
6 - 10 Installation & Operation Manual
Honeywell
6.8.2 Bay Alarms
NOTE: The
Grounding [Pause], Grounding [Shutdown], Overfill
[Pause], Overfill [Shutdown], Vapor Recovery [Pause], and
Vapor Recovery [Shutdown]
alarms come in pairs and
each pair is used to implement a single permissive.
Alarm Cause
Programmable input
1..6
The programmable input state (active/de-active) does not
match with the expected input state.
Transaction start error The new transaction cannot be started.
NOTE: The transaction cannot be managed/controlled due
to the internal MSC-L fatal fault. For example, missing or
failing hardware components.
Transaction stop error The running transaction cannot be stopped.
NOTE: The transaction cannot be managed/controlled due
to the internal MSC-L fatal fault. For example, missing or
failing hardware components.
Max. #batches
exceeded
No new batch can be started because the maximum number
of batches within a transaction is reached.
Grounding [Pause] The grounding permissive is detached.
Grounding [Shutdown] The grounding permissive is detached.
Overfill [Pause] The overfill protection permissive is detached.
Overfill [Shutdown] The overfill protection permissive is detached.
Vapor Recovery
[Pause]
The vapor recovery permissive is detached.
Vapor Recovery
[Shutdown]
The vapor recovery permissive is detached.