EasyManua.ls Logo

Honeywell Fusion4 MSC-L - 3.8.2.2 Characteristics; 3.8.3 Single Pulse Input; 3.8.3.1 Functional Description

Honeywell Fusion4 MSC-L
531 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System Description - Input Functions
Fusion4 MSC-L Part No.: 4418309_Rev09
3- 42 Installation & Operation Manual
Honeywell
3.8.2.2 Characteristics
3.8.3 Single Pulse Input
3.8.3.1 Functional Description
The function of the Single Pulse Input is to accept pulse signals from a
product stream single pulse flowmeter or an additive stream single
pulse flowmeter.
Item Minimum Typical Maximum Unit
Isolation voltage - - 3500 V
AC
Switching current (I
SW
) - - 10 mA
Input switching frequency - - 10 kHz
Input on time (T
ON
) 50 - - µs
Input off time (T
OFF
) 50 - - µs
External Device presence detec-
tion Voltage Level
0-5, 18-30 V
External Device absence detec-
tion Voltage Level
Floating Input (Open Contact), 9-14 V

Table of Contents

Related product manuals