Note: Stage 2 frames have a Rack Attention light on the frame control panel.
Rack Power Ready
Rack Attention
RV2A17
6
-2
Yes No
Go to step 3 of this procedure.
2. Go to System or Rack Cannot Become Powered Off in SY44-4934-00, FC 504x
Problem Analysis and Repair and Parts.
This ends the procedure.
3. Is the power off problem on the system unit?
No Yes
Go to step 6 of this procedure.
4. Ensure that the SPCN cables that connect the frames are connected and seated
correctly at both ends. Does the frame power off, and is the Power On light
off?
No Yes
This ends the procedure.
5. Go to step 9 on page 58 of this procedure.
6. Perform Powering Off the System (see Powering On and Powering Off the
System and Logical Partitions on page 922). Then return here and answer the
following question. Does the system unit or frame power off, and is the Power
On light off?
No Yes
The system is not responding to normal power off procedures, which
could indicate a Licensed Internal Code problem. Ask your next level
of support for assistance.
This ends the procedure.
7. Is the frame that will not power off part of a shared I/O Tower loop?
Yes No
Go to step 9 on page 58.
Power Problems
Chapter 1. Starting Problem Analysis 57