Troubleshooting and Maintenance
Troubleshooting
/Maintenance
153
Inspection
area
Inspection
item
Inspection
details
Inspection Cycle
Inspection
method
Judgment standard
Inspection
equipment
Daily
Regular
(Year)
1
2
2) Is there any
damage to cable
insulation?
Terminal
block
Is there any
damage?
Visual inspection
No abnormality
Smoothing
condenser
1) Is liquid
leaking inside?
2) Is the safety
apparatus in
position? Is there
any
protuberance?
3) Check the
power failure
capacity.
1), 2) Visual
inspection
3) Measure with
a capacity meter.
1),2) No
abnormality
3) Rated capacity
over 85%
Capacity meter
Relay
1) Is there any
chattering noise
during
operation?
2) Is there any
damage to the
contacts?
1), 2) Visual
inspection
1),2) No
abnormality
Braking
resistor
1) Is there any
damage from
resistance?
2) Check for
disconnection.
1) Visual
inspection
2) Disconnect
one side and
measure with a
tester.
1) No abnormality
2) Must be within
±10% of the rated
value of the
resistor.
Digital
multimeter /
analog tester
Do not perform a megger test (insulation resistance test) on the control circuit of the inverter.