8.7
Parameter Mode Communication Function
Group (COM)
Communication Function Group (PAR COM)
No.
Communi-
cation
Address
LCD Display
Name
Setting Range
Initial
Value
Shift in
Opera-
tion
Control
Mode
V
/
F
S
L
V
C
S
L
T
V
C
T
00
-
Jump Code
Jump code
0
99
20
O
O
O
O
O
O
01
0h1701
Int485 St ID
Built-in communication
inverter ID
1
250
1
O
O
O
O
O
O
02
0h1702
Int485 Proto
Built-in communication
protocol
0
ModBus RTU
0:
ModBus
RTU
O
O
O
O
O
O
1
--Reserved --
2
Serial Debug
03
0h1703
Int485 BaudR
Built-in communication
speed
0
1200 bps
3:
9600 bps
O
O
O
O
O
O
1
2400 bps
2
4800 bps
3
9600 bps
4
19200 bps
5
38400 bps
04
0h1704
Int485 Mode
Built-in communication
frame setting
0
D8/PN/S1
0:
D8/PN/S1
-
O
O
O
O
O
1
D8/PN/S2
2
D8/PE/S1
3
D8/PO/S1
05
0h1705
Resp Delay
Transmission delay
after reception
0
1000 (ms)
5 ms
O
O
O
O
O
O
06
Note29-1)
0h1706
FBus S/W Ver
Communication option
S/W version
-
1.00
O
O
O
O
O
O
07
0h1707
FBus ID
Communication option
inverter ID
0
255
1
O
O
O
O
O
O
08
0h1708
FBUS
BaudRate
FBus communication
speed
-
12 Mbps
O
O
O
O
O
09
0h1709
FieldBus LED
Communication option
LED status
-
-
O
O
O
O
O
O
30
0h171E
ParaStatus
Num
Number of output
parameters
0
8
3
O
O
O
O
O
O
31
0h171F
Para Stauts-1
Output address 1
0000-FFFF Hex
000A
O
O
O
O
O
O
32
0h1720
Para Stauts-2
Output address 2
0000-FFFF Hex
000E
O
O
O
O
O
O
33
0h1721
Para Stauts-3
Output address 3
0000-FFFF Hex
000F
O
O
O
O
O
O
34
0h1722
Para Stauts-4
Output address 4
0000-FFFF Hex
0000
O
O
O
O
O
O
35
0h1723
Para Stauts-5
Output address 5
0000-FFFF Hex
0000
O
O
O
O
O
O
36
0h1724
Para Stauts-6
Output address 6
0000-FFFF Hex
0000
O
O
O
O
O
O
37
0h1725
Para Stauts-7
Output address 7
0000-FFFF Hex
0000
O
O
O
O
O
O
38
0h1726
Para Stauts-8
Output address 8
0000-FFFF Hex
0000
O
O
O
O
O
O
* The grey cells indicate a hidden code which is only visible when setting a code.
Note 29-1)
COM 06
17 codes are displayed only when the communication module is installed.
Refer to the Options manual for options.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS SV-IS7 and is the answer not in the manual?

LSIS SV-IS7 Specifications

General IconGeneral
BrandLSIS
ModelSV-IS7
CategoryInverter
LanguageEnglish

Related product manuals