170
Control Function Group (PAR CON)
No.
Communi
-cation
Address
LCD Display
Name
Setting Range
Initial Value
Shift
in
Opera-
tion
1)Control Mode
V
/
F
S
L
V
C
S
L
T
V
C
T
70
0h1446
SS Mode
Speed search
mode selection
0
Flying Start - 1
0
X
O
O
O
X
X
1
Flying Start - 2
71
0h1447
Speed Search
Speed search
operation selection
Bit
0000-1111
0000
X
O
O
O
X
X
1
Speed search
selection on
acceleration
2
Restart after
trips
3
Restart after
instantaneous
interruption
4
Start
immediately
after power
On
72
Note21)
0h1448
SS Sup-
Current
Speed search
standard current
80
200 (%)
Below 75
kW
150
O
O
O
X
X
X
Above 90
kW
100
73
0h1449
SS P-Gain
Speed search
proportional gain
0
9999
100
O
O
O
X
X
X
74
0h144A
SS I-Gain
Speed search
integral gain
0
9999
200
O
O
O
X
X
X
75
0h144B
SS Block Time
Output
block time before
speed search
0
60 (sec)
1.0
X
O
O
X
X
X
77
0h144D
KEB Select
Energy buffering
selection
0
None
0:None
X
O
O
O
X
X
1
KEB-1
2
KEB-2
78
Note21)
0h144E
KEB Start Lev
Energy buffering
start level
110
200 (%)
125.0
X
O
O
O
X
X
79
0h144F
KEB Stop Lev
Energy buffering
stop level
130
210 (%)
130.0
X
O
O
O
X
X
80
0h1450
KEB Gain
Energy buffering
gain
1
2000
1000
O
O
O
O
X
X
82
Note22)
0h1452
ZSD
Frequency
Permanent
detection
frequency
0
10 (Hz)
2.00
O
X
X
O
X
O
83
0h1453
ZSD Band
Permanent
detection
frequency band
0
2 (Hz)
1.00
O
X
X
O
X
O
86
Note23)
0h1456
KEB P Gain
Energy buffering P
gain
0
20000
1000
O
O
O
O
X
X
87
0h1457
KEB I Gain
Energy buffering I
gain
1
20000
500
O
O
O
O
X
X
88
0h1458
KEB Slip Gain
Energy buffering
slip gain
0
2000.0 (%)
30.0
O
O
O
O
X
X
89
0h1459
KEB Acc Time
Energy buffering
acceleration time
0
600 (sec)
10.0
O
O
O
O
X
X