184
Applied Function Group (PAR APP)
No.
Communi-
cation
Address
LCD Display
Name
Setting Range
Initial Value
Shift in
Opera-
tion
Control Mode
V
/
F
S
L
V
C
S
L
T
V
C
T
21
0h1815
PID
F/B Source
PID feedback selection
0
V1
0:V1
X
O
O
O
X
X
1
I1
2
V2
3
I2
4
Int 485
5
Encoder
6
FieldBus
7
PLC
8
Synchro
9
Binary Type
22
0h1816
PID P-Gain
PID proportional gain
0-1000 (%)
50.0
O
O
O
O
X
X
23
0h1817
PID I-Time
PID integral time
0-200.0 (sec)
10.0
O
O
O
O
X
X
24
0h1818
PID D-Time
PID differential time
0-1000 (ms)
0
O
O
O
O
X
X
25
0h1819
PID F-Gain
PID feed forward gain
0-1000.0 (%)
0.0
O
O
O
O
X
X
26
0h181A
P Gain Scale
Proportional gain scale
0-100.0 (%)
100.0
X
O
O
O
X
X
27
0h181B
PID Out LPF
PID output filter
0-10000 (ms)
0
O
O
O
O
X
X
28
0h181C
PID Mode
PID mode select
0
Process PID
0:Process
PID
-
O
O
O
X
X
1
Normal PID
29
0h181D
PID Limit Hi
PID upper limit
frequency
PID lower limit
frequency (Hz)
300
(Hz)
60.00
O
O
O
O
X
X
30
0h181E
PID Limit Lo
PID lower limit
frequency
-300
PID upper limit
frequency (Hz)
-60.00
O
O
O
O
X
X
31
0h181F
PID Out Inv
PID output inverse
0
No
0:No
-
O
O
O
X
X
1
Yes
32
0h1820
PID Out
Scale
PID output scale
0.1
1000 (%)
100.0
X
O
O
O
X
X
34
0h1822
Pre-PID Freq
PID control period
movement frequency
0
maximum
frequency (Hz)
0.00
X
O
O
O
X
X
35
0h1823
Pre-PID Exit
PID control period
movement level
0
100 (%)
0.0
X
O
O
O
X
X
36
0h1824
Pre-PID
Delay
PID control period
movement delay time
0
9999 (sec)
600
O
O
O
O
X
X
37
0h1825
PID Sleep DT
PID sleep mode delay
time
0
999.9 (sec)
60.0
O
O
O
O
X
X
38
0h1826
PID Sleep
Freq
PID sleep mode
frequency
0
maximum
frequency (Hz)
0.00
O
O
O
O
X
X
39
0h1827
PID WakeUp
Lev
PID wake up level
0
100 (%)
35
O
O
O
O
X
X
40
0h1828
PID WakeUp
Mod
PID wake up mode
setting
0
Below Level
0:Below
Level
O
O
O
O
X
X
1
Above Level
2
Beyond Level
41
0h1829
PID Rev Run
En
PID reverse operation
0
No
0:No
X
O
O
O
X
X
1
Yes
42
0h182A
PID Unit Sel
PID control period unit
selection
0
%
0:%
O
O
O
O
X
X
1
Bar
2
mBar
3
Pa