recommended that less than 80% load is applied.
• IP54 product: -10–40℃
- No ice or frost should be present.
Relative humidity less than 90% RH (to prevent condensation
from forming)
Maximum 1000m above sea level for standard operation.
From 1000 to 4000m, the rated input voltage and rated
output current of the drive must be derated by 1% for every
100m.
Less than 5.9 m/sec
2
(0.6 G).
Prevent contact with corrosive gases, inflammable gases, oil
stains, dust, and other pollutants (Pollution Degree 2
Environment).
* UL Enclosed type 1 when an optional conduit box is installed. The 30–75 kW (200 V class) product is
regarded as UL Open type IP 20 when an optional conduit box is installed.