rial Operation Procedures
4
-
1
3
n
Parameter
Settings
for
Autotuning
The
following
parameters
must
be
set
before
autotuning.
*1.Not
normally
displayed.
Displayed
only
when
a
motor
switch
command
is
set
for
a
multi-function
digital
input
(one
of
H1-01
to
H1-05
set
to
16).
*2.Only
a
setting
of
2
(stationary
autotuning
for
line-to-line
resistance
only)
is
possible
for
V/f
control
or
V/f
control
with
PG.
*3.For
a
constant-output
motor,
set
the
value
at
the
base
speed.
*4.For
an
inverter
motor
or
vector
motor,
the
voltage
and
frequency
may
be
lower
than
for
a
general-purpose
motor.
Always
confirm
setting
on
the
name-
plate
or
in
test
reports.
Also,
if
you
know
the
no-load
values,
set
the
no-load
voltage
in
T1-03
and
the
no-load
frequency
in
T1-05
to
obtain
better
accu-
racy.
*5.Stable
vector
control
will
be
possible
when
the
setting
is
between
50%
and
100%.
*6.The
setting
range
depends
on
the
Inverter
capacity
and
the
setting
of
C6-01
(CT/VT
Selection).
Table 4.4 Parameter Settings before Autotuning
Param-
eter
Num-
ber
Name Display
Setting
Range
Factory
Setting
Data Displays during
Autotuning
V/f
V/f
with
PG
Open
Loop
Vector
T1-00
Motor
1/2
selection
Set
the
location
where
the
autotuned
motor
constants
are
to
be
stored.
1:
E1
to
E2
(motor
1)
2:
E3
to
E4
(motor
2)
*1
1
or
21YesYesYes
T1-01
Autotuning
mode
selec-
tion
Set
the
autotuning
mode.
0:Rotational
autotuning
1:
Stationary
autotuning
2:
Stationary
autotuning
for
line-to-
line
resistance
only
0
to
2
2
(V/f
and
V/f
with
PG)
0
(open-
loop
vec-
tor)
*2
Yes
(only
for
2)
Yes
(only
for
2)
Yes
T1-02
Motor
out-
put
power
Set
the
output
power
of
the
motor
in
kilowatts.
*3
10%
to
200%
of
Inverter
rated
output
*5
Same
as
Inverter
rated
output
Yes Yes Yes
T1-03
Motor
rated
voltage
Set
the
rated
voltage
of
the
motor
in
volts.
*3
*4
0
to
255.0
V
(200
V
class)
0
to
510.0
V
(400
V
class)
200.0
V
(200
V
class)
400.0
V
(400
V
class)
--Yes
T1-04
Motor
rated
current
Set
the
rated
current
of
the
motor
in
amps.
*3
10%
to
200%
of
Inverter
rated
cur-
rent
*5
Same
as
general-
purpose
motor
with
same
capacity
as
Inverter
Yes Yes Yes
T1-05
Motor
base
frequency
Set
the
base
frequency
of
the
motor
in
hertz.
*3
*4
0
to
400.0 Hz
*6
60.0
Hz - - Yes
T1-06
Number
of
motor
poles
Set
the
number
of
motor
poles. 2
to
48
poles 4
poles - - Yes
T1-07
Motor
base
speed
Set
the
base
speed
of
the
motor
in
r/min.
*3
0
to
24000
*6
1750
r/min
--Yes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3RV Series and is the answer not in the manual?

Omron SYSDRIVE 3G3RV Series Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3RV Series
CategoryInverter
LanguageEnglish

Related product manuals