5.4.1 Errors with error codes
Table 5-1 RFC 4072S error codes
Error code (hex) Error cause Remedy or response
0x8001 (0x9001)
to
0x8007 (0x9007)
Internal error
Please contact your nearest Phoenix Contact represen-
tative.
0x8008 (0x9008)
The boot project is missing or incom-
plete.
Check whether the non-safety-related project is
loaded on the standard controller.
If the non-safety-related project is not loaded
on the standard controller, download the
safety-related project to the iSPNS 3000 again.
If the non-safety-related project is not loaded
on the standard controller, follow the instruc-
tions in the note on “Order of project down-
loads” above this table.
0x8009 (0x9009)
to
0x8012 (0x9012)
Internal error
Please contact your nearest Phoenix Contact represen-
tative.
0x8013 (0x9013) The CPU load is higher than 90%.
Reduce the processor load.
Analyze the safety-related project. Optimize the
program code for better performance.
Avoid redundancies in the safety-related project so
that the CPU load is not increased unnecessarily.
Check if the maximum number of F-Devices to be
configured was exceeded. Reduce the number
according to the information in Section “Technical
data” on page 223, if necessary.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact RFC 4072S and is the answer not in the manual?

Phoenix Contact RFC 4072S Specifications

General IconGeneral
BrandPhoenix Contact
ModelRFC 4072S
CategoryController
LanguageEnglish

Related product manuals