0x812A (0x912A) Inconsistent process data description.
• Check process data assignment in your safety-
related project.
• Load the non-safety-related project to the standard
controller. Download the safety-related project to
the iSPNS 3000.
Follow the instructions provided in the note on
“Order of project downloads” above this table.
• If the error cannot be removed, please contact your
nearest Phoenix Contact representative.
0x812B (0x912B) Internal error
Please contact your nearest Phoenix Contact represen-
tative.
0x812C (0x912C)
Maximum number of supported F-
Devices exceeded.
Reduce the number of F-Devices connected to the
RFC.
0x812D (0x912D)
Internal error
Please contact your nearest Phoenix Contact represen-
tative.
0x812E (0x912E)
0x812F (0x912F)
The F-Destination address is invalid or
outside the permissible range.
• Check the F-Destination addresses used in the
project.
• If necessary, correct the corresponding addresses.
0x8130 (0x9130)
Maximum number of supported process
data descriptions exceeded.
Reduce the number of the process data descriptions.
0x8131 (0x9131)
to
0x8136 (0x9136)
Inconsistent process data description.
• Check the process data and process data assign-
ment.
• Load the non-safety-related project to the standard
controller. Download the safety-related project to
the iSPNS 3000.
Follow the instructions provided in the note on
“Order of project downloads” above this table.
• If the error cannot be removed, please contact your
nearest Phoenix Contact representative.
Table 5-1 RFC 4072S error codes
Error code (hex) Error cause Remedy or response