Errors, diagnostic messages and troubleshooting
108580_en_02 PHOENIX CONTACT 151 / 272
0x8137 (0x9137)
to
0x813C (0x913C)
Internal error
Please contact your nearest Phoenix Contact represen-
tative.
0x8141 (0x9141)
to
0x8150 (0x9150)
0x8161 (0x9161)
to
0x8165 (0x9165)
0x8181 (0x9181)
to
0x8186 (0x9186)
0x8241 (0x9241)
to
0x8247 (0x9247)
0x8248 (0x9248)
The supply voltage (24 V) is below the
specified range.
• Check the supply voltage.
• Make sure the supply voltage is OK.
0x8249 (0x9249)
The supply voltage (24 V) is above the
specified range.
• Check the supply voltage.
• Make sure the supply voltage is OK.
0x824A (0x924A)
to
0x824C (0x924C)
Internal error
Please contact your nearest Phoenix Contact represen-
tative.
0x824D (0x924D)
Ambient temperature is not in the speci-
fied range.
Check the ambient conditions (e.g., sufficient ventilation
in the control cabinet) and operate the RFC 4072S
within the range specified.
0x824E (0x924E)
to
0x825C (0x925C)
Internal error
Please contact your nearest Phoenix Contact represen-
tative.
0x8F00 (0x9F00)
to
0x8F02 (0x9F02)
0x8F03 (0x9F03)
to
0x8F07 (0x9F07)
Hardware fault.
0x8F08 (0x9F08)
to
0x8F0B (0x9F0B)
An error occurred during the firmware
upgrade.
Observe further instructions from a person instructed in
performing the update.
Table 5-1 RFC 4072S error codes
Error code (hex) Error cause Remedy or response