Safety notes for starting applications
Take the following into consideration when determining and programming the start condi-
tions for your machine or system:
– The machine or system may only be started if it can be ensured that nobody is present
in the danger zone.
– Meet the requirements of EN ISO 13849-1 with regard to the manual reset function. The
machine must not be set in motion and/or a hazardous situation must not be triggered
by the following actions, for example:
– Switching on safe devices
– Acknowledging device error messages
– Acknowledging communication errors
– Acknowledging block error messages in the application
– Removing startup inhibits for safety functions
Observe the following when programming/configuring the safety logic:
– Switching from the safe state (substitute value = 0) to the operating state can generate
an edge change (zero/one edge).
– In the safety logic, take measures to prevent this edge change resulting in unexpected
machine/system startup or restart.
Note for starting applications
Also observe these notes to prevent unexpected machine startup following acknowledg-
ment by means of operator acknowledgment.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact RFC 4072S and is the answer not in the manual?

Phoenix Contact RFC 4072S Specifications

General IconGeneral
BrandPhoenix Contact
ModelRFC 4072S
CategoryController
LanguageEnglish

Related product manuals