EasyManuals Logo

Phoenix Contact RFC 4072S User Manual

Phoenix Contact RFC 4072S
272 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #227 background imageLoading...
Page #227 background image
Technical data and ordering data
108580_en_02 PHOENIX CONTACT 227 / 272
Mechanical requirements
Vibration resistance in accordance with EN 60068-2-6/
IEC 60068-2-6
1g
Shock according to EN 60068-2-27/IEC 60068-2-27 20 g
Continuous shock according to EN 60068-2-27/
IEC 60068-2-27
5g
Safety characteristic data according to EN ISO 13849
Performance level (PL) e, maximum
Category 4, maximum
Probability of dangerous failure per hour (PFH
D
)1*10
-9
Diagnostic coverage (DC
avg
) 99 %
Mean time to dangerous failure (MTTF
D
) > 80 years
Safety characteristic data according to EN 62061
Safety integrity level claim limit (SIL CL) 3, maximum
Probability of a dangerous failure per hour (PFH
D
) 1*10
-9
Hardware fault tolerance (HFT) 1
Duration of use (mission time) 300 months, therefore no restrictions, no maintenance
intervals
Safe failure fraction (SFF) according to DIN EN 62061 99%
Safety characteristic data according to IEC 61508 – High demand
Safety Integrity Level (SIL) 3, maximum
Probability of dangerous failure per hour (PFH) 1*10
-9
Hardware fault tolerance (HFT) 1
Duration of use (mission time) 300 months, therefore no restrictions, no maintenance
intervals

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact RFC 4072S and is the answer not in the manual?

Phoenix Contact RFC 4072S Specifications

General IconGeneral
BrandPhoenix Contact
ModelRFC 4072S
CategoryController
LanguageEnglish

Related product manuals