Rockwell Automation Publication 193-UM015D-EN-P - February 2015 335
Metering and Diagnostics Chapter 8
configuration value for Power Scale (Parameter 377). When Single or Three
Phase (Parameter 176) is set to Three Phase, Total Reactive Power is calculated as
follows:
Total Reactive Power = (L1 Reactive Power + L2 Reactive Power + L3 Reactive
Power)
When Single or Three Phase (Parameter 176) is set to Single Phase, Total
Reactive Power is calculated as follows:
Total Reactive Power = (L1 Reactive Power + L2 Reactive Power)
Table 420 - Total Reactive Power (Parameter 71)
L1 Apparent Power
L1 Apparent Power (Parameter 72) reports the apparent power for line 1 in kVA
or MVA depending on the configuration value for Power Scale (Parameter 377).
When Voltage Mode (Parameter 352) is set to any Delta base setting, L1
Apparent Power is set to 0.
Table 421 - L1 Apparent Power (Parameter 72)
L2 Apparent Power
L2 Apparent Power (Parameter 73) reports the apparent power for line 2 in kVA
or MVA depending on the configuration value for Power Scale (Parameter 377).
When Voltage Mode (Parameter 352) is set to any Delta base setting, L2
Apparent Power is set to 0.
Default Value 0.000c
Minimum Value -2000000.000
Maximum Value 2000000.000
Parameter Type DINT
Size (Bytes) 4
Scaling Factor 1000
Units kVAR or MVAR
Default Value 0.000
Minimum Value 0.000
Maximum Value 2000000.000
Parameter Type DINT
Size (Bytes) 4
Scaling Factor 1000
Units kVA or MVA