Rockwell Automation Publication 193-UM015D-EN-P - February 2015 457
Specifications Appendix A
Electromagnetic
Compatibility Specifications
Performance Criteria 1 requires the DUT to experience no degradation or loss of performance.
Environment 2.
Table 516 - Electromagnetic Compatibility Specifications
Electrostatic Discharge Immunity
Test Level:
Performance Criteria:
8kV Air Discharge
6kV Contact Discharge
1 ➊➋
RF Immunity
Test Level:
Performance Criteria:
10V/m
1 ➊➋
Electrical Fast Transient/Burst Immunity
Test Level:
Performance Criteria:
4kV (Power)
2kV (Control and Comm)
1 ➊➋
Surge Immunity
Test Level:
Performance Criteria:
2kV (L-E)
1kV (L-L)
1 ➊➋
Radiated Emissions
Class A
Conducted Emissions
Class A