350 Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 8 Metering and Diagnostics
Table 458 - kVA Demand (Parameter 109)
Max kVA Demand
Max kVA Demand (Parameter 110) reports the maximum kVA Demand since
the last Max kVA Demand Reset command.
Table 459 - Max kVA Demand (Parameter 110)
Analog Monitor
The E300 Electronic Overload Relay’s Analog I/O Expansion Modules scan up
to three analog signals per module. This information can be used to monitor the
following analog applications:
Motor winding and bearing temperatures that are measured by RTD
sensors
Liquid, air, or steam flow
Tem p er atu re
Wei g ht
Vessel level
Potentiometer
PTC or NTC thermistor sensors
Analog Module 1
Analog Module 1 – Input Channel 00
Analog Module 1 – Input Channel 00 (Parameter 111) reports the monitored
value of Analog Module 1 – Input Channel 00.
Default Value 0.000
Minimum Value 0.000
Maximum Value 2000000.000
Parameter Type DINT
Size (Bytes) 4
Scaling Factor 1000
Units kVA
Default Value 0.000
Minimum Value 0.000
Maximum Value 2000000.000
Parameter Type DINT
Size (Bytes) 4
Scaling Factor 1000
Units kVA