T
he documentation matches the state of the machine, incl. the protective device
The verified configuration report corresponds to the desired project planning (see
"Verifying configuration", page 143)
The thorough checks must be carried out by qualified safety personnel or specially
qualified and authorized personnel and must be documented in a traceable manner.
In many cases, other data must be documented, see "Reports", page 144.
Additional thorough checks for EFI-pro
Chec
k EFI-pro connections and ensure they function as intended.
Check all settings related to EFI-pro in the configuration.
Recommended thorough checks
In man
y cases, it makes sense to carry out the following thorough checks during
commissioning and in certain situations:
Thorough check of the relevant points on the checklist, see "Checklist for initial
commissioning and commissioning", page 216
"Thorough visual check of the machine and the protective device", page 83
"Thorough check of the principal function of the protective device", page 81
"Thorough check of the area to be protected", page 81
"Test of the contour detection field", page 83
"Checking the collision protection field", page 83
Make sure that the operating personnel has been instructed in the protective
device’s function before starting work on the machine. The instruction is the
responsibility of the machine operator and must be carried out by qualified per‐
sonnel.
4.6.2 Planning the regular thorough check
Overview
T
he purpose of regular tests is to detect defects due to changes or external influences
(e.g. damage or manipulation) and to ensure that the protective measure provides the
necessary protection.
Important information
DANGER
H
azard due to lack of effectiveness of the protective device
Persons and parts of the body to be protected may not be recognized in case of
non-observance.
b
Carry out tests at least once a year.
b
Assign qualified safety personnel to carry out the tests or persons specifically
authorized for this purpose.
b
Document tests in a traceable manner.
Minimum requirements
T
he following thorough checks must be carried out at least once a year:
"Thorough check of the principal function of the protective device", page 81
Testing of the detection capability (resolution) in the context of the "Thorough
check of the area to be protected", page 81
4 P
ROJECT PLANNING
80
O P E R A T I N G I N S T R U C T I O N S | microScan3 Pro I/O 8025424/1ELL/2022-01-21 | SICK
Subject to change without notice

Table of Contents

Other manuals for SICK microScan3 Pro I/O

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK microScan3 Pro I/O and is the answer not in the manual?

SICK microScan3 Pro I/O Specifications

General IconGeneral
Scanning angle275°
Number of fields128
Dimensions102 mm x 152 mm x 106 mm
Number of safety outputs2
Number of OSSD outputs2
Scanning range5.5 m
Protective field range5.5 m
Resolution30 mm
Number of monitoring cases128
Response time60 ms
InterfacesEthernet, USB
Operating temperature+50 °C
Protection classIP65
Supply voltage24 V DC
Storage temperature+70°C
Operating voltage24 V DC (16.8 V DC ... 28.8 V DC)
Housing materialPlastic
Connection typeMale connector