Motor control
SIMOCODE pro
4-24 GWA 4NEB 631 6050-22 DS 03
4.2.5 "Reversing starter" control function
Description
With this control function, SIMOCODE pro can control the direction of
rotation of the motor (forwards and backwards).
Control commands
Start with "ON >" activates the QE1 contactor control (clockwise, i.e.
forwards)
Start with "ON <" activates the QE2 contactor control (counter-clockwise, i.e.
backwards)
Stop with "OFF" deactivates the QE1 and QE2 internal contactor controls.
The control commands can be issued to SIMOCODE pro from arbitrary
control stations (see also the description of "control stations"). Thus, the
inputs (plugs) must be connected to the corresponding sockets, preferably
to the "Enabled control command" sockets.
Every fault message causes the QE1 and QE2 contactor controls to be
deactivated.
Switching the direction of rotation
It is possible to switch the direction of rotation if the signal
"Status - ON >" or "Status - ON <" has expired (motor switched off) AND
after the interlocking time has elapsed:
Via the OFF control command.
Directly, when the
"Saving change-over command" is activated.
SIMOCODE pro prevents both contactors from switching on at the same
time. Switching from one direction of rotation to the other can be delayed
via the interlocking time.

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
Protection ClassIP20
Mounting TypeDIN rail mounting
Rated Operational Voltage24 V DC
Rated CurrentUp to 820 A
Protection FunctionsOverload, short-circuit, phase failure, asymmetry, ground fault, motor stall
Operating Temperature Range-25°C to +60°C
Communication ProtocolsPROFIBUS DP, PROFINET, Modbus RTU
Analog OutputsUp to 2
Temperature MonitoringPTC/KTY, RTD (PT100/PT1000)
Digital OutputsRelay outputs, Solid-state outputs
Analog Inputs0/4-20mA, PT100/PT1000

Related product manuals