Data formats and data records
SIMOCODE pro
B-30 GWA 4NEB 631 6050-22 DS 03
B.13 Data record 132 - Extended device parameters 1
Byte.
Bit
Designation
(PRM group)
Type Range Unit De-
fault
Note Informa-
tion
0.0 Reserved Byte[4]
4.0 Bit parameters (17)
4.0 3UF50 - Compatibility mode Bit 0, 1 0 BU2
4.1 3UF50 operating mode Bit 0, 1 0 0 = DPV0,
1 = DPV1
BU2
4.2 Reserved Bit 0
4.3 Reserved Bit 0
4.4 Reserved Bit 0
4.5 Reserved Bit 0
4.6 Reserved Bit 0
4.7 Reserved Bit 0
5.0 Reserved Bit 0
5.1 Reserved Bit 0
5.2 Reserved Bit 0
5.3 Reserved Bit 0
5.4 Analog module - Measuring range
Input
Bit 0, 1 0
0 = 0..20 mA
1 = 4-20 mA
AM
5.5 Analog module - Measuring range
Output
Bit 0, 1 0 AM
5.6 Reserved Bit 0
5.7 Reserved Bit 0
6.0
Overshooting/undershooting limit 1
Bit 0, 1 0 0 = ">"
(Overshooting)
1 = "<"
(Undershootin
g)
BU2
6.1
Overshooting/undershooting limit 2
Bit 0, 1 0 BU2
6.2
Overshooting/undershooting limit 3
Bit 0, 1 0 BU2
6.3
Overshooting/undershooting limit 4
Bit 0, 1 0 BU2
6.4 Line-to-line voltage Bit 0, 1 0 0 = No, 1 = Yes BU2
6.5 OPO level Bit 0, 1 0 0 = NO
Contact,
1 = NC
Contact
BU2
6.6 Positioner response for OPO Bit 0, 1 0 0 = CLOSED, 1
= OPEN
BU2
6.7 Star-delta - Transformer mounting Bit 0, 1 0 0 = Delta
1 = In supply
cable
7.0 External fault 5 - Level Bit 0, 1 0 0 = NO
Contact
1 = NC
Contact
BU2
7.1 External fault 6 - Level Bit 0, 1 0 BU2
7.2 Reserved Bit 0
7.3 Reserved Bit 0
7.4 Monitoring external fault 5 Bit 0, 1 0
0 = Always
1= Motor ON
BU2
7.5 Monitoring external fault 6 Bit 0, 1 0 BU2
Table B-14: Data record 132 - Extended device parameters 1