Outputs
SIMOCODE pro
6-4 GWA 4NEB 631 6050-22 DS 03
6.2 Basic unit outputs
Description
SIMOCODE pro has a "BU Outputs" function block with three relay outputs.
You can switch contactors or lamps via these relay outputs. For this, the
inputs (plugs) of the function block must be connected to the respective
sockets (usually the QE contactor controls of the control function). The "BU
Outputs" function block consists of:
• Three plugs corresponding to the relay outputs Out1 to Out3
• Three relays
• Output terminals.
Overall, there is one "BU Outputs" function block for BU1 and BU2.
Schematic
The following schematic shows the "BU Outputs" function block:
Fig. 6-2: "BU Outputs" function block
Application examples
• Control of the main contactor in the motor feeder:
You can, e.g., define which relay output is used for controlling the motor
contactor in the motor feeder. For this, connect the desired relay output to
the respective "QE." contactor control of the control function.
• Lamp control for displaying operating states:
You can define which relay outputs are to be used for controlling the
lamps/LEDs that display the operating states of the motor (Fault, ON,
OFF, Fast, Slow...).
To do this, connect the desired relay output to the respective "QE..."
contactor control of the control function. The following are specifically
intended for controlling lamps and LEDs:
In addition to the status displays, the "QL..." lamp controls automatically
signal via a 2Hz flash frequency:
– Test mode (QLE.../QLA lamp outputs are flashing)
– Unacknowledged fault (lamp output general fault QLS is flashing)
– Transfer of any other information, status information, warnings, faults
etc. to the relay outputs
1
2
BU Outputs
3
1
2
3
6
7
Out1
Out2
Out3
Output terminals
Terminal numbers
SIMOCODE pro